Exeltech XP1100 1100W Pure Sine Wave Inverter

EXELTECH XP1100 1100W Pure Sine Wave Inverter

XP 1100

(PDF)

XP1100 Exeltech Sine Wave Inverter

Features Comments
  • True Sine Wave
  • 1100 Watts AC Output
  • 12Vdc up to 108Vdc Output
  • Designed for Electronics
  • Ultra Lightweight
  • 21.5 Years MTBF
Made in America, the EXELTECH XP SERIES INVERTERS are the most affordable, reliable, lightweight and best regulated, true sine wave inverters available. The XP SERIES will operate any type of load. Everything you can plug into the wall can be operated by the XP SERIES. Available at 115Vac or 230Vac in 50, 60, or 400Hz.

Model Number Description
XPK-1-1-6 1100 Watt 12 VDC In 120 VAC / 60 Hz Output
XPK-1-2-6 1100 Watt 24 VDC In 120 VAC / 60 Hz Output
XPK-1-4-6 1100 Watt 48 VDC In 120 VAC / 60 Hz Output
XPK-3-1-5 1100 Watt 12 VDC In 230 VAC / 50 Hz Output
XPK-3-2-5 1100 Watt 24 VDC In 230 VAC / 50 Hz Output
XPK-3-4-5 1100 Watt 48 VDC In 230 VAC / 50 Hz Output
XPK-1-1-4 1100 Watt 12 VDC In 120 VAC /400 Hz Output
XPK-1-2-4 1100 Watt 24 VDC In 120 VAC /400 Hz Output
XPK-1-4-4 1100 Watt 48 VDC In 120 VAC /400 Hz Output
Other frequencies and voltages available

Output Power

Continuous Power Surge Power
No Load Power Output Voltage Output Current Weight (lbs)
1100W 2200W 20W 100 11.0 10
1100W 2200W 20W 117 9.5 10
1100W 2200W 20W 230 4.8 10

Input Power

Model Voltage Minimum (Typical) System (Typical) Maximum (Typical) Typical Efficiency @ Full Power Peak Efficiency @ 1/3 Power
12V 10.4/10.6V* 13.8V 16.5V 85% 87%
24V 19/21V* 27.6V 33V 87% 89%
32V 26.5/28V* 36.8V 44V 87% 89%
48V 41.5/42.5V* 55.2V 62V 87% 89%
66V 57.5/58.5V 75.9V 91V 88% 90%
108V 94/95V 125V 149V 88% 90%
*Shutoff Voltage/Buzzer Voltage

General

Conditions Minimum Typical Maximum
Waveform - Sinusoidal -
Voltage Output -5% Nominal +5%
Line Regulation - 0.1% 0.5%
Load Regulation - 0.5% 1%
Distortion - 1.5% 2%
Frequency -0.1% Nominal +0.1%

Mechanical

Width Height Depth
7.70" 3.60" 14.77"

CAD Drawing

PROTECTION CIRCUITRY

*Over Voltage: Shut off at maximum input voltage, per input conditions.

*Under Voltage: Shut off at minimum input voltage, per input conditions. Warning buzzer sounds before shutoff.

*Thermal: 105C internal temperature. warning buzz 5 C before shut off.

Output Short: Units shuts off and must be manually reset.

ENVIRONMENTAL

Temperature: -25 to 40 C full power derated above 40 C.

Humidity: 5 to 95% non condensing.

Altitude: -200 to 10k feet full power, derated above 10k.

Audible Noise: Less than 45 dbA

Cooling: Thermostatically controlled fan.

Finish: Painted aluminum.

Warranty: Full year parts and labor.

Extended Warranty: 5 year repair or replace unit for $100 per occurrence.


XP series model number XP-__-__-__-__

Step 1: Model number always starts with XP.

Step 2: To designate wattage enter the single character code from the wattage chart below.

WATTAGE CHART

Wattage 125 250 600 1100
Designation 1 2 6 K

Step 3: To designate output voltage enter the single character code from the Vac chart.

Vac OUTPUT VOLTAGE CHART

AC Volts 100 120 230
Designation 0 1 3

Step 4: To Designate input voltage enter the single character code from the Vdc Chart.

Vdc INPUT VOLTAGE CHART

DC Volts 12 24 32 36 48 66 108
Designation 1 2 B 3 4 E I

Step 5: To designate AC frequency enter the single character code from the AC frequency chart.

AC FREQUENCY CHART

Frequency

50Hz

60Hz

400Hz

Designation

5

6

4