IPD DC2-70 70W DC-DC Open Frame (Cover Optional) Converter


DC2-70
(PDF)

Features
  • High Efficiency
  • Advanced SMT Design
  • 18-36 VDC Input Range
  • 4250 VDC Input Range to Output Isolation meets reinforced insulation
  • Compact 2.5"x4.5"x1.2"
  • Fits 1U Applications
  • Optional Chassis & Cover
  • Safety Certified to EN 60950, EN 60601-1

Safety Specifications
us_ur.gif

Underwriters Laboratories File E137708

UL 60950 Third Edition
UL 60601-1 First Edition
CB Report Per IEC 60950:1999 Third Edition including all National Deviations
CB Report Per IEC 60601-1 (1988) Second Edition, A1, A2

us_ur.gif UL Recognition Mark for Canada File E137708 CAN/CSA-C22.2 No. 60950:00
CAN/CSA-C22.2 No. 601-1-M90
tuv.gif EN 60950:2000
EN 60601-1/A2:1995

Model Listing
Model # Output 1 Output 2 Output 3 Output 4
DC2-70-4001
DC2-70-4002
DC2-70-4003
DC2-70-4004
DC2-70-4005
DC2-70-4006
DC2-70-4007
+3.3V/6A
+5V/6A
+5V/6A
+5V/6A
+5V/6A
+5V/6A
+5V/6A
+5V/5A
+3.3V/5A
+3.3V/5A
-5V/5A
-5V/5A
+24V/2A
+24V/2A
+12V/2A
+12V/2A
+15V/2A
+12V/2A
+15V/2A
+12V/2A
+15V/2A
-12V/2A
-12V/2A
-15V/2A
-12V/2A
-15V/2A
-12V/2A
-15V/2A
DC2-70-3001
DC2-70-3002
+5V/6A
+5V/6A
+12V/2A
+15V/2A
  -12V/2A
-15V/2A
DC2-70-2001
DC2-70-2002
DC2-70-2003
DC2-70-2004
DC2-70-2005
+3.3V/6A
+5V/6A
+5V/6A
+12V/3A
+15V/3A
+5V/5A
+12V/4A
+24V/2A
-12V/3A
-15V/2A
   
DC2-70-1001
DC2-70-1002
DC2-70-1003
DC2-70-1004
DC2-70-1005
DC2-70-1006
DC2-70-1007
DC2-70-1008
2.5V/14A
3.3V/14A
5V/14A
12V/5.8A
15V/4.7A
24V/2.9A
28V/2.5A
48V/1.5A

 

 

1


Output Specifications
Total Output Power at 50ºC 50W
70W
Convection Cooled
300 LFM Forced Air Cooled
Output Voltage Centering (50% Load)

Output 1:
Output 2:
Output 3:
Output 4:

±0.5%
±5.0%
±5.0%
±5.0%
Output Voltage Adjust Range Output 1: 95-105%
Load Regulation Output 1:
Output 2:
(4001-5)
(2001)
Output 3:
Output 4:
0.5% (10-100% load change)
5.0% (10-100% load change)
8.0% (10-100% load change)
8.0% (10-100% load change)
5.0% (10-100% load change)
5.0% (10-100% load change)
Source Regulation Outputs 1-4: 0.5%
Cross Regulation Outputs 2-4: 4.0%
Output Noise
Outputs 1-4 1.0%

Transient Response
Voltage Deviation
Recovery Time
Load Change

Outputs 1-4
5.0%
500S
50% to 100%
 
Output Overvoltage Protection Output 1: 110% to 150%
Output Overpower Protection 110-160% rated Pout, cycle on/off, auto recovery
Start Up Time 4 seconds

Input Specifications
Input Voltage Range 18-36VDC
Input Under-Voltage Lockout
Turn-On Voltage
Turn-Off Voltage

14.5-17.5.0VDC
14.0-17.0.0VDC

Input Overvoltage Shutdown

37.0-43.0.0VDC
Mazimum Input Current 5.5A
Reflected Ripple Current 5%
Efficiency 78% Typ., Full Power, 24VDC, varies by model

Environmental Specifications
Ambient Operating Temperature Range 0ºC to +70ºC
Derating: See Power Rating Chart
Ambient Storage Temperature Range -40ºC to +85ºC
Temperature Coefficient Outputs 1-4: 0.02%/ºC
Vibration MIL-STD-810E, Method 514.4, Category 1
Shock Transit drop per MIL -STD-810E, Method 516.4, Procedure IV

General Specifications
Dielectric Strength 4242 VDC, Primary to Secondary, 1 sec.
2121 VDC, Primary to Ground, 1 sec
707VDC, Secondary to Ground, 1 Sec
Good Power Signal Logic high with input voltage above Vin min.
Remote Sense (Singles Only) 250mV compensation of output cable losses
Mean-Time Between Failures 100,000 Hours min, MIL-HDBK-217F, 25ºC, GB
Weight 0.60 Lbs Open Frame
1.00 Lbs Chassis & Cover


[ Last Updated: ]
© 2006 Current Solutions, Inc. All rights reserved.
Contact Us | User Agreement