The APC-A1000 series power shelf is intended for operation with the APC-3000-R series power modules. These modules convert the AC input power to a regulated, low-noise DC bus voltage. Modules are available with 750W, 800W, or 1000W.
Oring diode is used at the output of each module to prevent the module from bringing down the bus voltage either during hot insertion or as the result of a module fault. The connectors between the power module and the shelf are selected to prevent from blind mating and support hot insertion and removal. Active current sharing between paralleled modules and shelves distribute the load evenly between multiple power units.
FAULT AND STATUS REPORTING
The APC-AXXX series of power modules provide a number of status report and remote control features. Those signals are aggregated on the host interface on the back of the shelf. Please refer to the module's data sheet for a detailed definition of each signal. Host interface is optional for the shelf.
FAULT MANAGEMENT
The modules are fully protected from damaging ether the load or themselves under single fault or abnormal operating conditions.
| Fault or Abnormal Condition |
Response |
| AC Input surges and transients |
The robust design of these units provides superior immunity to AC line transients and surges. |
| Loss of AC Input Power |
The module will continue operation without interruption or assertion of the POWER FAIL WARNING signal within 1/2 cycle of outages of main power. Typical hold up time is 20ms. |
| Output Overvoltage |
Under any single fault condition, the output voltage will not exceed 64V. |
| Internal Overheating |
The module is fully protected against damage from excessive heat. The unit will automatically recover once it has cooled down. |
| Output Overload |
When output currents exceeds maximum limi the module goes into a constant power mode and output voltage falls. The unit will run in hiccup mode when the output voltage is below 39V (±2V). |
VISUAL INDICATORS
Each power module (APC-A1000 or APC-800) has two LEDs to provide visual status information. Please see the following table for these indicators.
| Name |
Color Illumination |
Meaning |
LED 1
AC OK |
Green |
Input Voltage OK |
LED 2
Output OK
or
Output Fail |
Green
Amber |
Unit powered up and operating normally
or
Unit has detected and internal fault or overload condition. |
EMI PERFORMANCE