PowerStax APC-A0750 750W AC-DC Power Module


APC-A0750

AC-DC Power Module

(PDF)


Description

The APC-A0750 series of front-end power modules is specifically designed to operate as an integral part of a completed distributed power system, with or without battery backup.

A full complement of protection, alarm and control features has been incorporated into the power unit to provide the versatility of applications.

When up to 3 x APC-A0750 are used with the 1U high APC-2250 19" rack, a total of 2,250 Watts (or 1,500W of N+1) of 24 VDC or 28 VDC output can provide a low profile, flexible and scalable solution.

The versatile feature set makes this front end power module an excellent choice for applications requiring modular AC-to_DC power systems such as distributed power and DC UPS.


Features
  • High power density, 7.7W / in³
  • Net weight: < 2.2KG
  • Low profile: 40.8mm (fits 1U 19" shelf - APC-R2250 series)
  • Efficiency: 77% - 86% typical
  • Power factor correction (meets IEC1000-3-2 requirements)
  • Overvoltage and overcurrent protection
  • Overtemperature warning and protection
  • Redundant parallel operation - up to 12 units
  • Remote On/Off and Remote sense
  • Active load sharing
  • Hot insertion / removal (Hot swap)
  • Power fail warning and fault alarm
  • Low start-up temperature: -30°C
  • I²C for voltage, current, temperature report and power supply ID.
  • Front panel LED indicators
  • 400Hz available (with wattage derating)
  • Meets UL60950, EN60950 and CE mark requirements

Applications
  • Advanced workstations
  • Telecom / Datacom equipment
  • Midrange computers
  • Mainframes
  • File servers
  • LAN / WAN applications
  • Mass storage (SANs)

Environmental Characteristics
Parameter
Min
Typ
Max
Unit
Notes
Storage
-40
-
85
°C
Operating Temperature
0
-
60
°C
Derating (TBD)
Acoustics
-
47
52
dBA
ISO7779 SPL
Humidity
(non-condensing)
5
-
95
%
Altitude
-200
-
13000
feet
Derated at 2°C/1000ft. above 8000Ft
ESD
-
-
-
-
IEC1000-4-2 Level 3 stand alone
Isolation voltage
3000VAC
Primary to Secondary
1500VAC
Primary to chassis GND
1500VAC
Secondary to chassis ground
MTBF
4 x 10ª (a=5)
-
-
hours
@110V input, 80% load, Ta = 30°C
Vibration
Meet IEC68-2-6
Shock
Meet IEC68-2-36
Weight
-
2.2
-
Kg


[ Last Updated: ]
© 2006 Current Solutions, Inc. All rights reserved.
Contact Us | User Agreement